Contact Sensor Type Vibration Monitoring System (VM-9301 Series)

Permanent vibration monitoring for systems such as motor, pump and blower.
Monitoring system suitable for multi-channel measurement.
Frequency range, measurement range or output signal can be customized.

Features

■ Mixed implementation with the conventional system “VM-9201” is possible
Mixed implementation with the conventional system “VM-9201” is possible
■ A wide variety of pickups

Selectable from electrodynamic velocity pickup or piezoelectric accelerometer.

Electrodynamic velocity pickup

Specialized in medium frequency (up to 1,000 Hz) vibration detection. Correspond to velocity monitor.

Type VP-3144 C/D VP-3354 A VP-3364 A VP-3134 A VP-3213 AC/AD VP-3133 H/V
Sensitivity 10mV/(mm/s) 10mV/(mm/s) 10mV/(mm/s) 10mV/(mm/s) 17.5mV/(mm/s) 17.5mV/(mm/s)
Natural
frequency
14Hz 14Hz 14Hz 14Hz 4.5Hz 4.5Hz
Operational
temperature
range
-20 to +80 °C -20 to +80 °C -20 to +80 °C -10 to +70 °C -20 to +70 °C -10 to +70 °C
Structure Drip-proof Water-proof Water-proof Flame-proof Drip-proof Flame-proof
Outward
appearance
VP-3144 C/D

Type C

VP-3354 A VP-3364 A VP-3134 A VP-3213 AC/AD

Type AC

VP-3133 H/V
Notes High sensitivity/
medium frequency
Medium frequency /
2-directional
Medium frequency /
3-directional
Medium frequency Low frequency /
horizontal only
Low frequency /
H (horizontal only),
V (vertical only)
Piezoelectric accelerometer

Specialized in high frequency (over 1,000 Hz) vibration detection. Correspond to acceleration monitor.

Type VP-A51 IW VP-4135 VP-A4345Ⅰ
Sensitivity 5mV/(m/s2) 5mV/(m/s2) 5mV/(m/s2) ±10%
Natural frequency 30,000 Hz 8,000 Hz 25,000 Hz
Operational temperature range -30 to +110 °C -10 to +60 °C -20 to +80 °C
Structure Water-proof Flame-proof Safe and explosion proof ⅡBT4
Outward
appearance
VP-A51ⅠW VP-4135 VP-A4345Ⅰ
Notes Insulated
■ Multi-channel
Maximum 12 channel per 1 system is available. Range and function can be set individually per every channel.

Application examples

Cable is drawed from pickups located at large sized motor at hope power generator to a monitoring system inside of the control panel. Monitoring systems can monitor vibration values and send out the alarm in an emergency.

Application example

Specifications

Type VM-9301 series VM-9301A series
Pickup Electrodynamic velocity pickup Piezoelectric accelerometer
Amplifier
unit type
Type 1 line :VA-9301(1-I)
Select velocity or displacement
Type 2 line :VA-9301(2-I)
Simultaneous measurement of velocity and displacement
Type 1 line VA-9301A(1-I)
Select acceleration, velocity or displacement
Type 2 line :VA-9301A(2-I)
Simultaneous measurement of any two of acceleration, velocity or displacement
Frequency
range
Low: 5 to 500Hz (-11 to +6%)
Medium:10 to 500Hz (-11 to +6%)
Filter selectable (pass band)

High-pass filter :5, 10, 15, 20, 50, 100Hz
Low-pass filter :20, 50, 100, 200, 500Hz
5 to 10kHz (-30 to +6%)
Filter selectable (pass band)

High-pass filter :5, 10, 20, 50, 100Hz
Low-pass filter :100, 200, 500, 1k, 5k, 10kHz

(High-pass filter : 20Hz- in case of displacement
or velocity
Low-pass filter : -500Hz in case of displacement,
-1kHz in case of velocity)

Measurement
range
Displacement 50, 100, 150, 200, 300, 500, 999 (1,000) μmP-P 100, 150, 200, 300, 500, 999 (1,000) μmP-P
Velocity 10, 15, 20, 30, 50 mm/s 10, 15, 20, 30, 50 mm/s
Acceleration 10, 15, 20, 30, 50, 100, 150, 200, 300, 500 m/s2
Equipment
failure
Indication
lamp
Orange LED located on the upper part of amplifier front panel [FAT] Secondary power is lit at ubnormal condition.
Alarm
contact
1a contact (open at normal condition) operate under fuse melting, power switch shut off and primary / secondary power failure
Alarm reset Select from automatic or manual recovery
Pickup
cable
break
alarm
Indication
lamp
Green LED located on the upper part of amplifier front panel [PU] Lights-out when wire is broken (lights-on at normal condition)
(When pickup connected with charge amplifier is used, this function is not valid.)
Alarm
contact
Standard:1a contact *available 1b or 1c (open at normal condition, closed when wire is broken) operate when pickup cable is broken.
Alarm reset Select from automatic or manual recovery
Alarm Alarm step Type 1 line: upper limit 2 steps Alarm (ALM) / Trip (TRP)
Type 2 line: upper limit 1 step Alarm1 (ALM1,1lline), Alarm2(ALM2, 2line)
Delay timer Select from 0 to 15 sec. by the slide switch inside of the amplifier unit (0 sec. if not specified.)
Setting
extent
5.0 to 99.9% (can be set at 0.1% intervals)
(When alarm function is not used 99.9% is set. Indication lamp and contact is on at over full scale value)
Indication
lamp
Type 1 line: Orange LED [ALM], red LED [TRP] Type 2 line: Orange LED [ALM1], red LED [ALM2]
Alarm
Contact
Select from “ALM / ALM1 circuit:2a contact TRP / ALM2 circuit 2a contact” or
“ALM / ALM1 circuit:1b1a contact TRP / ALM2 circuit 1a1b contact”
Contact capacity AC110 V 2 A (DSP Relay made by Panasonic) DC30 V 0.2 A
Alarm reset Select from automatic (Hysteresis 3%) or manual recovery
Rectification
level
output
DC
output 1
Select from DC4-20mA (insulation output), Loading 500Ω or less or
DC1-5 V (insulation output), Loading 100kΩ or more
DC
output 2
Select from DC4-20mA (insulation output), Loading 500Ω or less or
DC1-5 V (insulation output), Loading 100kΩ or more
Waveform
output
Pickup
waveform
output
AC±10mV /(mm/s) or AC±17.5mV /(mm/s),
Loading 100kΩ or more
(Depending on specifications of pickup)
AC±5mV/(m/s2), Loading 100kΩ or more
(Depending on specifications of pickup)
Waveform
output
AC±5V(at the full-scale), Loading 100kΩ or more
Panel meter Red LED three-digit indication, [9.9.9] is displayed at over 120% of full-scale
Operational temperature
range
0 to 50 °C, 20 to 95%RH, wet bulb temperature is 35°C (non-condensing)
Power supply Available range AC85 to 264V, 47 to 66Hz
Power
consumption
20VA or less (1CH), 30VA or less (3CH), 45VA or less (6CH), 60VA or less (9CH), 75VA or less (12CH)
At AC100V (Depends on the number of amplifier or power supply)
Painting color Munsell 5Y7/1, half matted
Mass Approx. 2.0kg (1CH), approx. 3.9kg (3CH), approx. 5.9kg (6CH), approx. 8.2kg (9CH),
approx. 10.2kg (12CH)

External dimensions

External dimensions

Unit:mm

A B C D E F G H I
Type 1 channel 90 170 300 88 132 90 148 162 50
Type 3 channel 210 149 300 160 132 180 143 100 195
Type 6 channel 300 149 300 250 132 270 143 100 285
Type 9 channel 390 149 300 340 132 360 143 100 375
Type 12 channel 480 149 300 430 132 450 143 100 465